What is voltage drop?
Every cable has some resistance, so the voltage at the load is lower than at the source. Too much drop makes lights dim, motors run hot and equipment fail. A common guide is to keep the drop under 3 percent on a branch circuit and under 5 percent for the whole installation.
Choose the conductor material and wire size, enter the supply voltage, current and one-way length, and the calculator shows the voltage drop in volts and percent, the voltage at the load and the power lost as heat. If the result is above the limit, use a thicker wire or a shorter run. Always check local electrical rules.
The formula and worked examples
The calculator uses voltage drop = k × current × resistance per 1,000 ft × length in feet ÷ 1,000. Here k is 2 for a single phase circuit, because the current goes out and comes back, and about 1.732 (the square root of 3) for a three phase circuit. The length you enter is one way. Aluminium resistance is taken as 1.61 times copper.
- 12 AWG copper, 230 V single phase, 16 A, 30 m: the drop is about 6.2 V, or 2.7 percent, which is inside the 3 percent guide.
- 14 AWG copper, 230 V single phase, 20 A, 30 m: the drop is about 12.4 V, or 5.4 percent, which is too much. A thicker wire is needed.
- 10 AWG copper, 400 V three phase, 25 A, 50 m: the drop is about 8.8 V, or 2.2 percent.
Limits of this calculator
This is a quick estimate and not a design tool. It uses typical resistance values for copper at 75 °C and sizes in AWG. It ignores cable reactance, power factor, the temperature of your cable, bundled cables and long runs in conduit. It also does not check whether the wire can safely carry the current, which depends on the insulation, the way the cable is installed and local rules. Always follow your local electrical code and ask a qualified electrician for real installations.
Common questions
How can I reduce voltage drop? Use a thicker wire, shorten the cable run, lower the current, or use a higher supply voltage.
Why is the length one way? The calculator already counts the return path through the factor k, so enter only the distance from the source to the load.
Is 3 percent a legal limit? No. It is a common guide for branch circuits. The limits in your country's rules can be different.